Cox Aerial Solutions LLC

Executive Thermal Inspection Summary Report

Thermal Intelligence for Safer, More Reliable Infrastructure

FAA Part 107 Certified UAS OperationsElectrical Thermal Inspection Capabilities$2,000,000 Liability Insurance Coverage

Customer Information

Customer / Utility

Prairie Valley Electric Cooperative

Project

Distribution Line Thermal Reliability Assessment

Inspection Program

Annual Utility Partnership Program – Tier 3

Inspection Date

July 18, 2026

Inspection Area

Rural Distribution Circuit 14-27

Inspection Provider

Cox Aerial Solutions LLC

Inspection Platform

DJI Matrice 4T Radiometric Thermal UAS

Inspection Overview

Cox Aerial Solutions LLC completed an aerial thermal inspection of the assigned distribution system utilizing FAA-compliant UAS operations, radiometric thermal imaging technology, and high-resolution visual documentation.

The inspection was performed to identify abnormal thermal conditions, document asset condition, and provide actionable information to support preventative maintenance planning and system reliability.

Inspection Coverage

Distribution Line Inspected13.4 Miles
Utility Structures Reviewed126
Electrical Assets Evaluated312
Thermal Images Captured486
Visual Images Captured512
Total Findings Identified3

Overall System Condition Summary

Inspection Condition RatingAssetsStatus
Normal Operation309Operating within expected thermal range
Monitor2Continue observation during routine maintenance
Maintenance Recommended1Schedule corrective evaluation
Critical Findings0No immediate critical concerns identified

Key Finding Identified

Finding ID

CAS-PVE-2026-0718-001

Asset: Primary Distribution Connection

Structure: PV-1427-083

Circuit: 14-27

Voltage Class: 13.8 kV

Thermal analysis identified an elevated temperature condition at the conductor connection hardware.

Maximum Recorded Temperature: 147°F

Temperature Differential: +65°F above reference conditions

Recommended Action

Cox Aerial Solutions LLC recommends:

  • Ground-level evaluation of connection hardware
  • Verification of connection integrity
  • Inspection for corrosion or deterioration
  • Corrective maintenance if required

Recommended Maintenance Priority: Scheduled Maintenance Review

Reliability Impact

The identified condition may represent an increased electrical resistance concern and could contribute to future equipment degradation if left unresolved.

Early identification allows the utility to:

  • Prioritize maintenance activities
  • Reduce unexpected failures
  • Improve system reliability
  • Better allocate field resources

Recommended Future Action

Cox Aerial Solutions LLC recommends continued inspection cycles to establish historical asset condition tracking and identify developing issues before they impact system reliability.

Recommended monitoring approach:

  • Annual thermal inspection cycles
  • Repeat asset comparisons
  • Condition tracking of identified equipment
  • Preventative maintenance planning

Report Conclusion

Based on the aerial thermal inspection completed by Cox Aerial Solutions LLC, the inspected infrastructure is operating within acceptable conditions with one identified asset requiring scheduled maintenance review.

Continued thermal monitoring will provide additional visibility into asset performance and support proactive infrastructure management.

Cox Aerial Solutions LLC

Professional Aerial Solutions Built on Safety, Precision, and Integrity

Report Number: CAS-PVE-2026-0718-001

Prepared For: Prairie Valley Electric Cooperative

Prepared By: Cox Aerial Solutions LLC